===================== Product Identification =====================
MSDS NAME:52742, FIRE EXTINGUISHER,VAPORIZING LIQUID.
NIIN:01-107-3298
MSDS Number: CGDXZ
=== Responsible Party ===
Company:ANSUL INC
Address:ONE STANTON ST
City:MARINETTE
State:WI
ZIP:54143-2542
Country:US
Info Phone Num:715-735-7411
Emergency Phone Num:715-735-7411,800-424-9300(CHEMTRAC)
CAGE:MO936
=== Contractor Identification ===
Company:ANSUL INC
Address:ONE STANTON STREET
Box:City:MARINETTE
State:WI
ZIP:54143-2542
Country:US
Phone:715-735-7411
CAGE:03670
Company:ANSUL INC
Address:ONE STANTON ST
Box:City:MARINETTE
State:WI
ZIP:54143-2542
Country:US
Phone:715-735-7411
CAGE:MO936
============= Composition/Information on Ingredients =============
Name:BROMOTRIFLUOROMETHANE (HALON 1301) (SARA 313) (CERCLA)
CAS:75-63-8
RTECS #:PA5425000
Fraction by Wt: >99%
Other REC Limits:NONE RECOMMENDED
OSHA PEL:1000 PPM
ACGIH TLV:1000 PPM; 9596
Ozone Depleting Chemical:1
===================== Hazards Identification =====================
LD50 LC50 Mixture:ORAL LD50 (RAT) IS >800,000 PPM(V/V)4HR.
Routes of Entry: Inhalation:YES Skin:YES Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:EYES: LIQUID CAN PRODUCE CHILLING AND
DISCOMFORT. SKIN: EVAPORATION FROM SKIN CAN PRODUCE CHILLING.
FROSTBITE CAN OCCUR. INHALATION: CAN CAUSE SUFFOCATION BY REDUCING
OXYGEN AVAILABLE.MAY LEAD TO NARC OSIS,CARDIAC
IRREGULAITIES,UNCONSCIOUSNESS,DEATH. INGESTION: NOT LIKELY TO OCCUR
SINCE MATERIAL IS A GAS AT ROOM TEMP.
Explanation of Carcinogenicity:NONE
Effects of Overexposure:ACUTE: DIZZINESS, IMPAIRED COORDINATION,
REDUCED MENTAL ACUITY, AND CARDIAC EFFECTS CAN OCCUR.
UNCONSCIOUSNESS OR EVEN DEATH IN HIGH CONCENTRATIONS WITH LONGER
EXPOSURES. CHRONIC: NONE KNOWN WHEN OCCU PATIONAL EXPOSURES ARE
BELOW THE TLV.
Medical Cond Aggravated by Exposure:CARDIAC PROBLEMS.
======================= First Aid Measures =======================
Eyes: FLUSH WITH LARGE AMOUNTS OF WATER. IF REDNESS, ITCHING,
OR BURNING SENSATION DEVELOPS, GET MEDICAL ATTENTION. TREAT FOR
FROSTBITE IF NECESSARY. SKIN: WASH AREA WITH SOAP AND WATER. IF
REDNESS, I TCHING, OR BURNING OCCURS, GET MEDICAL ATTENTION. TREAT
FOR FROSTBITE IF NECESSARY. INHALATION: MOVE TO FRESH AIR. IF NOT
BREATHING,GIVE CPR. IF BREATHING DIFFICULT,GIVE OXYGEN. GET MEDICAL
ATTENTION.
===================== Fire Fighting Measures =====================
Flash Point:NONE
Extinguishing Media:THIS IS A FIRE EXTINGUISHING AGENT.
Fire Fighting Procedures:USE WATER TO COOL FIRE-EXPOSED CYLINDERS OF
EXTINGUISHING AGENT.USE SCBA WITH FULL FACEPIECE AND PROTECTIVE
CLOTHING WHEN ENTERING FIRE AREAS WHERE AGENT USED.
Unusual Fire/Explosion Hazard:AGENT CONTAINERS EQUIPPED WITH PRESS/TEMP
RELIEF DEVICES, BUT RUPTURE MAY OCCUR UNDER FIRE CONDITIONS AND
TOXIC BY-PRODUCTS MAY BE FORMED IN FIRES OVER 900F.
================== Accidental Release Measures ==================
Spill Release Procedures:EVACUATE AREA. VENTILATE TO OUTSIDE
ATMOSPHERE. COOL OR REMOVE HOT METAL SURFACES OR SOURCE OF
NON-EXTINGUISHED FLAMES.
Neutralizing Agent:NONE SPECIFIED BY MANUFACTURER.
====================== Handling and Storage ======================
Handling and Storage Precautions:STORE AS A LIQUEFIED COMPRESSED GAS
AWAY FROM HIGH TEMPERATURES.
Other Precautions:STORE AWAY FROM ACTIVE METALS AND FIRES INVOLVING
METAL HYDRIDES.
============= Exposure Controls/Personal Protection =============
Respiratory Protection:NOT NORMALLY NECESSARY IF CONTROLS ARE ADEQUATE.
FOR HIGH CONCENTRATIONS EXCEEDING 10% OR IF EXPOSURE IS PROLONGED,
USE POSITIVE PRESSURE AIR-SUPPLIED RESPIRATOR.
Ventilation:LOCAL EXHAUST RECOMMENDED. MECHANICAL (GENERAL) IS
RECOMMENDED IN LOW AREAS OR INDOORS WHERE VAPORS MAY COLLECT.
Protective Gloves:PLASTIC IF WORKING WITH LIQUID.
Eye Protection:GOGGLES. FULL FACESHIELD IF SPLASHING.
Other Protective Equipment:EYEWASH STATION AND SAFETY SHOWER ARE GOOD
SAFETY PRACTICE IN WORK AREAS WHEN WORKING WITH LIQUAFIED PRODUCT.
Work Hygienic Practices:NONE SPECIFIED BY MANUFACTURER.
Supplemental Safety and Health
NONE
================== Physical/Chemical Properties ==================
HCC:G3
Boiling Pt:B.P. Text:-72F,-58C
Vapor Pres:188.0 PSI
Vapor Density:5.2 AIR=1
Spec Gravity:1.57
pH:UNKNON
Evaporation Rate & Reference:N/A GAS AT ROOM TEMP.
Solubility in Water:NEGLIGIBLE
Appearance and Odor:COLORLESS GAS. SWEET ODOR.
Percent Volatiles by Volume:100
================= Stability and Reactivity Data =================
Stability Indicator/Materials to Avoid:YES
ACTIVE METALS AND FIRES INVOLVING METAL HYDRIDES.
Stability Condition to Avoid:DECOMPOSES UNDER FIRE CONDITIONS ABOVE
900F.
Hazardous Decomposition Products:THERMAL DECOMPOSITION AT TEMP. ABOVE
900F FORMING HYDROGEN FLUORIDE AND HYDROGEN BROMIDES.CAN RESULT IN
INJURY OR DEATH.
Conditions to Avoid Polymerization:WILL NOT OCCUR.
==================== Disposal Considerations ====================
Waste Disposal Methods:DISPOSE OF IN ACCORDANCE WITH LOCAL, STATE AND
FEDERAL REGULATIONS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.