MSDS NAME:HALON GLC-13B1
NIIN:00F046191
MSDS Number: BYMQQ
=== Responsible Party ===
Company:E/M CORP SUB OF GREAT LAKES CHEM CORP
Address:2801 KENT AVE
Box:2400
City:WEST LAFAYETTE
State:IN
ZIP:47906-0400
Country:US
Info Phone Num:317-497-6100/501-862-5141
Emergency Phone Num:317-497-6100/501-862-5141
CAGE:8F024
=== Contractor Identification ===
Company:E / M CO. DIV OF MORGAN CHEMICAL PRODUCTS INC
Address:100 COOPER CIR
Box:3969
City:PEACHTREE CITY
State:GA
ZIP:30269
Country:US
Phone:770-261-4835 / FAX: 770-631-0833
CAGE:8F024
============= Composition/Information on Ingredients =============
Routes of Entry: Inhalation:YES Skin:NO Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:INHALATION: MAY CAUSE ANESTHETIC &
CARDIAC EFFECTS AT CONCENTRATIONS >10% BY VOLUME. PROLONGED
EXPOSURE TO CONCENTRATIONS >10% (15-20%) MAY LEAD TO POSSIBLE
DEATH.
Explanation of Carcinogenicity:NONE
Effects of Overexposure:INTOXICATION, UNCONSCIOUSNESS
Medical Cond Aggravated by Exposure:CARDIAC CONDITIONS.
======================= First Aid Measures =======================
First Aid:INHALATION: REMOVE TO FRESH AIR. GIVE CPR/OXYGEN IF
NECESSARY. SKIN: FLUSH W/WATER. EYES: FLUSH W/WATER. OBTAIN MEDICAL
ATTENTION IN ALL CASES. NOTE: EPINEPHRINE IS CONTRAINDICATED IN THE
TREATMENT OF OVER-EXPOSURE TO THIS PRODUCT.
===================== Fire Fighting Measures =====================
Flash Point:NON-FLAMMABLE
Extinguishing Media:WATERSPRAY/MEDIA SUITABLE FOR FLAMMABLE MATERIALS
IN THE AREA.
Fire Fighting Procedures:WEAR SELF CONTAINED BREATHING APPARATUS. USE
WATER SPRAY TO COOL CYLINDERS INVOLVED IN FIRES.
Unusual Fire/Explosion Hazard:>1000F, HALON MAY RELEASE HYDROGEN
FLUORIDE, HYDROGEN BROMIDE, CARBONYL FLUORIDE & CARBONYL BROMIDE.
Spill Release Procedures:EVACUATE AREA. WEAR SELF CONTAINED BREATHING
APPARATUS. VENTILATE ENCLOSED AREAS IN CASE OF DISCHARGE.
====================== Handling and Storage ======================
Handling and Storage Precautions:PROTECT CYLINDERS FROM PHYSICAL
DAMAGE. STORAGE TEMPERATURE SHOULDN'T EXCEED 125F. CYLINDERS SHOULD
BE SECURED STORED W/VALVE PROTECTION CAP IN PLACE.
Other Precautions:DETERMINE THAT PIPING IS EMPTY BEFORE DOING
MAINTENANCE WORK. PERIODICALLY CHECK CYLINDERS TO ENSURE VALVES
AREN'T LEAKING. AVOID PROLONGED EXPOSURE TO EXCESSIVE
CONCENTRATIONS.
Respiratory Protection:WEAR NIOSH APPROVED, SELF CONTAINED BREATHING
APPARATUS AT CONCENTRATIONS >10,000 PPM.
Ventilation:LOCAL EXHAUST: FOR MATERIAL TRANSFER & HANDLING. MECHANICAL
(GENERAL): FOR INDOOR AREAS.
Protective Gloves:LINED NEOPRENE/LEATHER
Eye Protection:CHEMICAL SAFETY GOGGLES
Other Protective Equipment:NONE
Work Hygienic Practices:DON'T WEAR CONTACT LENSES.
Supplemental Safety and Health
Boiling Pt:B.P. Text:-72F
Melt/Freeze Pt:M.P/F.P Text:-270F
Vapor Pres:62
Vapor Density:5.1
Spec Gravity:1.57
Solubility in Water:0.03%/WT
Appearance and Odor:COLORLESS GAS W/NO ODOR
================= Stability and Reactivity Data =================
Stability Indicator/Materials to Avoid:YES
ACTIVE METALS, FIRES OF METAL HYDRIDES & MATERIAL CONTAINING OWN OXYGEN
Stability Condition to Avoid:FLAMES, HOT SURFACES, SMOKING
Hazardous Decomposition Products:HYDROGEN FLUORIDE, HYDROGEN BROMIDE,
BROMINE, CABONYL FLUORIDE, CARBONYL BROMIDE
Waste Disposal Methods:RETURN CYLINDERS TO GREAT LAKES CHEMICAL
CORPORATION, EL DORADO, ARKANSAS. DISPOSE OF IN ACCORDANCE W/LOCAL,
STATE & FEDERAL REGULATIONS. NON-FLAMMABLE GAS UN1956. UN1009.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.