===================== Product Identification =====================
MSDS NAME:RECYCLED HALON 1301 (SEE SUPPL DATA)
NIIN:00-168-5737
Status Code:A
MSDS Number: CKQTM
=== Responsible Party ===
Company:PACIFIC SCIENTIFIC CO HTL/KIN-TECH DIVISION
Address:1800 HIGHLAND AVE
City:DUARTE
State:CA
ZIP:91010
Country:US
Info Phone Num:818-359-9317/602-796-1100
Emergency Phone Num:1-800-227-8431 (INFOTRACK)
Preparer's Name:WILLIAM MESERVE
CAGE:05167
=== Contractor Identification ===
Company:PACIFIC SCIENTIFIC CO HTL/KIN-TECH DIVISION
Address:1800 HIGHLAND AVE
Box:City:DUARTE
State:CA
ZIP:91010
Country:US
Phone:818-359-9317/602-796-1100
CAGE:05167
============= Composition/Information on Ingredients =============
Name:TRIFLUOROBROMOMETHANE
CAS:75-63-8
RTECS #:PA5425000
= Wt:100.
OSHA PEL:6100 MG/M3;1000 PPM
ACGIH TLV:6090 MG/M3;1000 PPM
Ozone Depleting Chemical:1
===================== Hazards Identification =====================
LD50 LC50 Mixture:INHALATION (RAT) ALC(15 MIN) = 83.2%
Routes of Entry: Inhalation:YES Skin:YES Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:INHALATION: OVEREXPOSURE MAY CAUSE
CENTRAL NERVOUS SYSTEM DEPRESSION SUCH AS DIZZINESS, CONFUSION,
INCOORDINATION, DROWSINESS OR UNCONSCIOUSNESS. THIS MATERIAL MAY
CAUSE HEIGHTENED SENSITIVITY TO CIRC ULATING EPINEPHRINE
(ADRENALINE) COMPOUNDS RESULTING IN IRREGULAR HEART BEATS AND
SOMETIMES DEATH. SKIN/EYE CONTACT: EVAPORATION OF HALON 1301 ON THE
SKIN/EYE MAY CAUSE A CHILLING SENSATION OR EVEN FR OSTBITE.
SIGNIFICANT SKIN PERMEATION AND SUBSEQUENT SYSTEMIC TOXICITY
APPEARS UNLIKELY.
Explanation of Carcinogenicity:NOT LISTED BY IARC, OSHA OR ACGIH AS A
CARCINOGEN.
Effects of Overexposure:CENTRAL NERVOUS SYSTEM DEPRESSION AND/OR HEART
IRREGULARITIES. INHALATION: DIZZINESS, CONFUSION, INCOORDINATION,
DROWSINESS OR UNCONSCIOUSNESS, IRREGULAR HEART BEATS. SKIN/EYE
CONTACT: EVAPORATION OF HALON 1301 ON THE SKIN/EYE MAY CAUSE A
CHILLING SENSATION OR EVEN FROSTBITE
Medical Cond Aggravated by Exposure:NONE SPECIFIED BY MANUFACTURER.
======================= First Aid Measures =======================
First Aid:INHALATION: REMOVE TO FRESH AIR IMMEDIATELY; KEEP PERSON
CALM. IF BREATHING IS DIFFICULT, GIVE OXYGEN. IF NOT BREATHING,
GIVE ARTIFICIAL RESPIRATION. CALL PHYSICIAN. ADMINISTRATION OF
EPINEPHRINE (ADR ENALINE) IS CONTRAINDICATED IN THE TREATMENT OF
OVEREXPOSURE TO HALON 1301. SKIN CONTACT: IMMEDIATELY FLUSH AREA
WITH LARGE AMOUNT OF LUKEWARM, NOT HOT WATER. IF PERSISTENT
REDNESS, ITCHING, OR BURNIN G SENSATION EXISTS, SEEK MEDICAL
ATTENTION. EYE CONTACT: IMMEDIATELY FLUSH AFFECTED EYE(S) WITH
LUKEWARM, NOT HOT WATER FOR AT LEAST 15 MINUTES. CONSULT A
PHYSICIAN.
===================== Fire Fighting Measures =====================
Flash Point:NON-FLAMMABLE
Extinguishing Media:HALON 1301 IS A FIRE EXTINGUISHING AGENT. USE WATER
TO COOL FIRE-EXPOSED CYLINDERS AS THEY MIGHT RUPTURE WHEN EXPOSED
TO HEAT.
Fire Fighting Procedures:SELF CONTAINED BREATHING APPARATUS AND
PROTECTIVE CLOTHING SHOULD BE WORN WHEN RE-ENTERING UNVENTILATED
FIRE AREAS WHERE THE PRODUCT HAS BEEN USED.
Unusual Fire/Explosion Hazard:WHEN HALON 1301 IS DISCHARGED ONTO A
FIRE, IT DECOMPOSES ABOVE 1560F (850C), RELEASING HYDROGEN
FLUORIDE, HYDORGEN BROMIDE, BROMINE, & SMALL AMOUNTS OF CARBONYL
FLUORIDE, & CARBONYL BROMIDE. THESE PRO DUCTS ARE HARMFUL IF
INHALED, ARE EASILY DETECTED; ONLY A FEW PARTS PER MILLION CAUSE AN
UNPLEASANT, ACRID ODOR.
================== Accidental Release Measures ==================
Spill Release Procedures:EVACUATE AREA. WEAR PROTECTIVE GEAR WHEN
TURNING OFF GAS SOURCE. BEFORE RE-ENTRY, VENTILATE AREA, ESPECIALLY
LOW OR ENCLOSED PLACES WHERE HEAVY VAPORS MIGHT COLLECT.
Neutralizing Agent:NONE SPECIFIED BY MANUFACTURER.
====================== Handling and Storage ======================
Handling and Storage Precautions:STORE CYLINDERS IN COOL PLACE, BELOW
125F. AVOID CYLINDER DAMAGE. LIMIT EXPOSURE TO VAPORS.
Other Precautions:NONE SPECIFIED BY MANUFACTURER.
============= Exposure Controls/Personal Protection =============
Respiratory Protection:NOT NORMALLY NEEDED IF CONTROLS ARE ADEQUATE. IF
NEEDED, USE MSHA/NIOSH APPROVED RESPIRATOR FOR ORGANIC VAPORS. FOR
HIGH CONCENTRATIONS, CONFINED AREAS, AND OXYGEN-DEFICIENT
ATMOSPHERES, WEAR AIR-SUPP LIED MASK OR SELF-CONTAINED BREATHING
APPARATUS.
Ventilation:VENTILATE LOW-LYING AREAS, SUCH AS SUMPS OR PITS WHERE
DENSE VAPORS MAY COLLECT. USE LOCAL EXHAUST TO CONTROL EXPOSURES.
Protective Gloves:LINED BUTYL GLOVES
Eye Protection:CHEMICAL SPLASH GOGGLES WHEN HANDLING LIQUID.
Other Protective Equipment:NONE REQUIRED.
Work Hygienic Practices:NONE SPECIFIED BY MANUFACTURER.
Supplemental Safety and Health
P/N: 30402103. THIS MSDS IS FOR HALON 1301 USED IN THE FIRE
EXTINGUISHER. FOR MSDS ON CARTRIDGE (P/N:30903824), SEE MSDS# CKQTL
(HCC=E2). NOTE: HCC OF E2 IS AT HIGHER ARCHY THAN G3. BOTH MSDS
MUST BE CONSULTED AT THE SAME TIME.
================== Physical/Chemical Properties ==================
HCC:G3
Boiling Pt:=-57.8C, -72.F
Vapor Pres:235 PSIA
Vapor Density:5.14 @ 25C
Spec Gravity:1.54 @ 25C
Solubility in Water:0.03% BY WEIGHT @ 25C
Appearance and Odor:COLORLESS GAS WITH SLIGHT ODOR.
================= Stability and Reactivity Data =================
Stability Indicator/Materials to Avoid:YES
ACTIVE METALS, FIRES OF METAL HYDRIDES, AND MATERIALS CONTAINING OWN
OXYGEN.
Stability Condition to Avoid:NONE KNOWN.
Hazardous Decomposition Products:HYDROGEN FLUORIDE, HYDROGEN BROMIDE.
=================== Toxicological Information ===================
Toxicological Information:INHALATION: RAT ALC (15 MINUTES)= 83.2%.
CANINE CARDIAC NOAEL = 5.0%; CANINE LOAEL = 7.5%.
==================== Disposal Considerations ====================
Waste Disposal Methods:DISPOSE OF IN ACCORDANCE WITH ALL LOCAL, STATE,
AND FEDERAL REGULATIONS. IN SOME REGIONS, DISCHARGE FOR NON-FIRE
RELATED EVENTS IS PROHIBITED. UNUSED PRODUCT SHOULD BE RETURNED FOR
RECYCLING TO PACIFI C SCIENTIFIC, DUARTE, CALIFORNIA.
=================== MSDS Transport Information ===================
Transport Information:DOT SHIPPING NAME: BROMOTRIFLUOROMETHANE,
NON-FLAMEABLE GAS, 2.2, UN1009
===================== Regulatory Information =====================
SARA Title III Information:SARA TITLE III HAZARD CATEGORIES AND LISTS:
THIS CHEMICAL IS SUBJECT TO THE REPORTING REQUIREMENTS OF SEC 313
OF TITLE III OF SUPERFUND AND 40 CFR PART 372. CHRONIC HEALTH = NO;
ACUTE HEALTH = YES; FI RE HAZARD = NO; PRESSURE HAZARD = YES;
REACTIVITY=NO; EXTREMELY HAZARDOUS SUBSTANCE= NO; CERCLA HAZ
SUBSTANCE= NO; TOXIC CHEMCALS=NO.
======================= Other Information =======================
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.
*** END OF RECORD *** |
|