===================== Product Identification =====================
MSDS NAME:AVIATION TURBINE FUEL,AVIATION
NIIN:00-256-8617
MSDS Number: BDPGW
=== Responsible Party ===
Company:ATLANTIC RICHFIELD COMPANY
Address:515 S. FLOWER ST
Box:2679
City:LOS ANGELES
State:CA
ZIP:90053
Country:US
CAGE:8P176
=== Contractor Identification ===
Company:ATLANTIC RICHFIELD CO
Address:515 S. FLOWER ST
Box:2679
City:LOS ANGELES
State:CA
ZIP:90053
Country:US
Phone:213-486-2687
CAGE:8P176
============= Composition/Information on Ingredients =============
Name:JP-4 AIRCRAFT TURBINE FUEL
RTECS #:NY9340000
Fraction by Wt: 100%
Other REC Limits:USAF 8HR TWA 200 PPM
===================== Hazards Identification =====================
Effects of Overexposure:EYE IRRITATION,SKIN IRRITATION LOADING TO
DERMATITIS,CENTRAL NERVOUS SYS.DEPRESSION,CHEM.PENUMONIA.
======================= First Aid Measures =======================
Eyes:FLUSH W/CLEAN LOW PRESS.WATER FOR AT LEAST 15
MINS.SKIN:THOROUGHLY WASH AFFECTED AREA WITH SOAP & WATER.REMOVE
CONTAMINATED CLOTHING & THOROUGHLY CLEAN BEFORE REUSE.INHAL:REMOVE
TO FRESH AIR.INGE ST:DO NOT INDUCE VOMITING.SEE DR.
===================== Fire Fighting Measures =====================
Flash Point:10F
Lower Limits:1.3
Upper Limits:8.0
Extinguishing Media:FOAM,DRY CHEMICAL & CO*2.
Fire Fighting Procedures:USE SELF-CNTND BRTHG APPARATUS,USE PROT.
EQ.CONF.AREA
Unusual Fire/Explosion Hazard:FLAMM.VAPORS NORM TEMPS & PRESS.VAPORS
MIXED IN CERT. PROPORTIONS W/AIR CAN BURN OR EXPLODE-C.AREAS
================== Accidental Release Measures ==================
Spill Release Procedures:REMOVE ALL SOURCES OF IGNITION AROUND SPILL
AREA. CLEAN UP SPILL AS SOON AS POSSIBLE.STOP DISCHARGE IF
POSSIBLE.KEEP PEOPLE AWAY.AVOID CONTACT WITH LIQUID.ISOLATE &
REMOVE DISCHARGED MATERIAL.
====================== Handling and Storage ======================
Handling and Storage Precautions:SWITCH LOADING:A STATIC IGNITION HAZ.
CAN EXIST WHEN LOW PRESSURE(VAP) PRODUCTS(DIESEL,JET FUEL,ETC;)ARE
LOADED INTO A CARGO TANK THAT CONT.FLAMM.VAPO
Other Precautions:SWITCH LOADING REQUIRES SPECIAL PRECAUTIONS THAT ARE
IN ELECTRICAL EQUIPT.SHOULD BE INSTALLED IAW MATL ELECTRIC
CODE.KEEP CONTS CLOSED.AVOID VAPORMST.
============= Exposure Controls/Personal Protection =============
Respiratory Protection:NONE REQD UNDER ADEQUATE VENT;OTHERWISE USE
NIOSH/MESA APPD.RESPIRTR
Ventilation:USE ADEQUATE VENTILATION
Protective Gloves:IMPERVIOUS
Eye Protection:CHEM GOGGLES
Other Protective Equipment:IMPERVIUS BOOTS,APRONS, & FACIAL PROTECTION.
Supplemental Safety and Health
================== Physical/Chemical Properties ==================
HCC:F2
Boiling Pt:B.P. Text:235F
Vapor Pres:30
Vapor Density:5
Spec Gravity:0.78
Solubility in Water:NEGLIGIBLE
Appearance and Odor:COLORLESS TO LIGHT AMBER COLOR-ODOR PETROLEUM NAPH
================= Stability and Reactivity Data =================
Stability Indicator/Materials to Avoid:YES
STRONG ACIDS,ALKALIES, & OXIDIZERS SUCH AS LIQ. CL*2 & O*2
Stability Condition to Avoid:HEAT & OPEN FLAME
Hazardous Decomposition Products:INCOMPLETE COMBUSTION. PRODUCT CO.
==================== Disposal Considerations ====================
Waste Disposal Methods:USE ABSORBENT MATERIAL SUCH AS CLAY OR
DIATOMACEOUS EARTH TO CLEAN UP SPILL.DISPOSE OF CONTAMINATED
MATERIAL IN AN APPROVED DISPOSAL SITE.COMPLY WITH FEDERAL,STATE,&
LOCAL REGULATIONS CONCERNING WASTE DISPOSAL TO LANDFILLS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.
*** END OF RECORD *** |
|