SAFETY DATA SHEET according to EC directive 2001/58/EC
SUVA 庐 236fa Refrigerant
Version 2.1
Revision Date 13.10.2004 Ref. 130000000816
This SDS adheres to the standards and regulatory requirements of Great Britain and may not meet the regulatory
requirements in other countries.
1. IDENTIFICATION OF THE SUBSTANCE/PREPARATION AND OF THE COMPANY/UNDERTAKING
Product information
庐
Product name : SUVA 236fa Refrigerant
Use of the : refrigerant
Substance/Preparation
Company : DuPont de Nemours (Nederland) B.V.
Dordrecht Works
Baanhoekweg 22
3313 LA Dordrecht
Telephone : +31786301720
Telefax : +31786301192
Emergency telephone : +44-(0)2871-861.313
number
2. COMPOSITION/INFORMATION ON INGREDIENTS
Chemical Name CAS-No. EC-No. Classification Concentration [%]
1,1,1,3,3,3-Hexafluoropropane 690-39-1 425-320-1 >= 99
3. HAZARDS IDENTIFICATION
Rapid evaporation of the liquid may cause frostbite.
Vapours are heavier than air and can cause suffocation by reducing oxygen available for breathing.
4. FIRST AID MEASURES
General advice : If unconscious place in recovery position and seek medical advice. Never give
anything by mouth to an unconscious person. If breathing is irregular or
stopped, administer artificial respiration. If symptoms persist, call a physician.
Inhalation : Move to fresh air. Keep patient warm and at rest. Artificial respiration and/or
oxygen may be necessary.
Skin contact : Wash off with warm water. Take off all contaminated clothing immediately.
Eye contact : Rinse thoroughly with plenty of water, also under the eyelids. Consult a
physician.
Notes to physician
Treatment : Do not give adrenaline or similar drugs.
5. FIRE-FIGHTING MEASURES
Specific hazards during fire : pressure build-up
fighting
1/5
SAFETY DATA SHEET according to EC directive 2001/58/EC
SUVA 庐 236fa Refrigerant
Version 2.1
Revision Date 13.10.2004 Ref. 130000000816
Special protective : In the event of fire, wear self-contained breathing apparatus.
equipment for fire-fighters
Further information : Use extinguishing measures that are appropriate to local circumstances and the
surrounding environment. Cool containers / tanks with water spray.
6. ACCIDENTAL RELEASE MEASURES
Personal precautions : Evacuate personnel to safe areas. Ventilate the area. Refer to protective
measures listed in sections 7 and 8.
Environmental precautions : Should not be released into the environment.
Methods for cleaning up : Evaporates.
7. HANDLING AND STORAGE
Handling
Advice on safe handling : Provide sufficient air exchange and/or exhaust in work rooms. For personal
protection see section 8.
Advice on protection : No special protective measures against fire required.
against fire and explosion
Storage
Requirements for storage : Keep container tightly closed in a dry and well-ventilated place. Store in original
areas and containers container.
Advice on common storage : No materials to be especially mentioned.
German storage class : 2A : Compressed, liquefied or pressurised gas
8. EXPOSURE CONTROLS / PERSONAL PROTECTION
Engineering measures
Ensure adequate ventilation, especially in confined areas.
Personal protective equipment
Respiratory protection : For rescue and maintenance work in storage tanks use self-contained breathing
apparatus. Vapours are heavier than air and can cause suffocation by reducing
oxygen available for breathing.
Hand protection : heat insulating gloves
Eye protection : safety glasses
Hygiene measures : Handle in accordance with good industrial hygiene and safety practice.
2/5
SAFETY DATA SHEET according to EC directive 2001/58/EC
SUVA 庐 236fa Refrigerant
Version 2.1
Revision Date 13.10.2004 Ref. 130000000816
9. PHYSICAL AND CHEMICAL PROPERTIES
Form : compressed liquefied gas,
Colour : colourless,
Odour : slight, ether-like,
pH : neutral
Melting point/range : -103 掳C at 1 013 hPa
Boiling point/range : -2 掳C at 1 013 hPa
Flash point : does not flash
Explosive properties : Not explosive
Vapour pressure : 2 490 hPa at 25 掳C
Vapour pressure : 3 500 hPa at 50 掳C
Density : 1,370 g/cm3 at 22 掳C, (as liquid)
Density : 0,0057 g/cm3 at 25 掳C (1 013 hPa)
Water solubility : 0,724 g/l at 25 掳C
Partition coefficient (n- : POW: 1,12
octanol/water)
10. STABILITY AND REACTIVITY
Conditions to avoid : The product is not flammable in air under ambient conditions of temperature
and pressure. When pressurised with air or oxygen the mixture may become
flammable. Certain mixtures of HCFCs or HFCs with chlorine may become
flammable or reactive under certain conditions.
Materials to avoid : alkali metals, alkaline earth metals, powdered metals, powdered metal salts
Hazardous decomposition : hydrogen halides, carbon dioxide (CO2), Carbon monoxide, fluorocarbons,
products carbonyl halides
11. TOXICOLOGICAL INFORMATION
Acute inhalation toxicity
鈥? 1,1,1,3,3,3- : LC50/4 h/rat : 2 841 mg/l
Hexafluoropropane
Human experience : Excessive exposures may affect human health, as follows:
3/5
SAFETY DATA SHEET according to EC directive 2001/58/EC
SUVA 庐 236fa Refrigerant
Version 2.1
Revision Date 13.10.2004 Ref. 130000000816
Inhalation
severe shortness of breath, narcosis, Irregular cardiac activity
Further information : Rapid evaporation of the liquid may cause frostbite.
12. ECOLOGICAL INFORMATION
Elimination information (persistence and degradability)
Biodegradability : //28 d/ 16 %
According to the results of tests of biodegradability this product is not readily
biodegradable.
Toxicity to fish
鈥? 1,1,1,3,3,3- : LC50/96 h/Zebra fish: 292 mg/l
Hexafluoropropane
Toxicity to algae
鈥? 1,1,1,3,3,3- : EC50/96 h/Algae: 299 mg/l
Hexafluoropropane
Aquatic toxicity
鈥? 1,1,1,3,3,3- : EC50/48 h/Daphnia: > 186 mg/l
Hexafluoropropane
13. DISPOSAL CONSIDERATIONS
Product : Can be used after re-conditioning.
Contaminated packaging : Empty pressure vessels should be returned to the supplier.
14. TRANSPORT INFORMATION
ADR
Class: 2
Classification Code: 2A
HI No:: 20
UN-No: 3163
Labelling No.: 2.2
Proper shipping name: Liquefied gas, n.o.s. (1,1,1,3,3,3-Hexafluoropropane)
IATA_C
Class: 2.2
UN-No: 3163
Labelling No.: 2.2
Proper shipping name: Liquefied gas, n.o.s. (1,1,1,3,3,3-Hexafluoropropane)
4/5
SAFETY DATA SHEET according to EC directive 2001/58/EC
SUVA 庐 236fa Refrigerant
Version 2.1
Revision Date 13.10.2004 Ref. 130000000816
IMDG
Class: 2.2
UN-No: 3163
Labelling No.: 2.2
Proper shipping name: Liquefied gas, n.o.s. (1,1,1,3,3,3-Hexafluoropropane)
15. REGULATORY INFORMATION
Labelling according to EC Directives
The product does not need to be labelled in accordance with EC directives or respective national laws.
16. OTHER INFORMATION
Further information
Before use read DuPont鈥檚 safety information., For further information contact the local DuPont office or DuPont鈥檚
庐
nominated distributors., DuPont鈥檚 registered trademark
The information provided in this Safety Data Sheet is correct to the best of our knowledge, information and belief at
the date of its publication. The information given is designed only as a guidance for safe handling, use, processing,
storage, transportation, disposal and release and is not to be considered a warranty or quality specification. The
information relates only to the specific material designated and may not be valid for such material used in
combination with any other materials or in any process, unless specified in the text.
Other
5/5
|