Jeffrey S. Moquin, Director Telephone: 754-321-3200
Risk Management Department Facsimile: 754-321-3290
August 10, 2005
TO: Mrs. Angela Iudica, Principal
Silver Shores Elementary School
FROM: Robert J. Krickovich, Coordinator, LEA
Facilities and Construction Management, Environmental Division
SUBJECT: Indoor Air Quality (IAQ) Assessment
FISH 150, 151, 152, 155, 228, 229 and 231
On July 22, 2005 the IAQ Assessment Team conducted an assessment of FISH 150, 151, 152, 155, 228,
229 and 231 at Silver Shores Elementary School. The evaluation consisted of a walkthrough of the
identified areas to assess the current condition of the location with regard to indoor air quality. This
assessment included observations of the carpet, floor tile, ceiling tile, interior walls, false ceiling
plenum, and accessible ventilation equipment.
Attached are the findings of this assessment along with recommendations for further assessment,
remediation, or corrective actions, if needed.
Generally, the IAQ Assessment did not identify any existing conditions significantly impacting IAQ
and thereby presenting immediate health and safety concerns to building occupants. However, due to
individual sensitivities and predisposing health factors, it is possible that some building occupants
may elicit a health response to agents and / or conditions identified during the evaluation. Therefore,
to further improve IAQ, prevent development of future IAQ-related problems, and to reduce the
potential for IAQ-related complaints by building occupants, the IAQ Assessment Team recommends
appropriate follow up of each item identified and listed in the attached evaluation.
Should any questions arise, or if the current concerns continue after the attached recommendations
have been addressed, please feel free to contact me at 754-321-1638.
cc: Sam Gregg, Area Superintendent
Steven Friedman, Area Director
Jeffrey S. Moquin, Director, Risk Management
Angelino Garcia, Project Manager II, Facilities and Construction Management
Steve Feldman, Broward Teachers Union
Mark Dorsett, Manager 1, Physical Plant Operations Division, Zone 1
Roy Norton, Manager Custodial/Grounds, Physical Plant Operations Division
RK/tc
Enc.
The School Board of Broward County, Florida
IAQ Assessment
July 21, 2005
Evaluation Requested
Silver Shores Elementary School
July 22, 2005
Evaluation Date
12:15 pm
Time of Day
Outdoor Conditions Temperature 91.1 53
Relative Humidity Ambient CO2 450
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
150 68.9 67.6 415 4
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In One tile above door
Ceiling Type No
Yes
Drywall
Wall Type None
No
No
12 x 12 Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling
No Yes Yes Clean as appropriate
Walls
Flooring Yes No No
HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant
HVAC Return Grills Yes No No
Ceiling at Supply No Yes Yes Clean with Wexcide disinfectant
Grills
Surfaces in Room No Yes Yes Clean as appropriate
Observations
Findings:
- Stained ceiling tile above door
- Heavy dust accumulation on walls, desks and cabinets
- Dust and debris on HVAC supply grills
- Dust and debris on ceiling at HVAC supply grills
- Dust and debris on environmental surfaces
- Elevated humidity level and low temperature
- Half a gallon of bleach found
Recommendations:
Site Based Maintenance:
- Replace stained ceiling tile
- Clean/dust all walls, desks and cabinets as appropriate
- Clean HVAC supply grills with Wexcide disinfectant solution
- Clean ceiling at HVAC supply grills as appropriate
- Clean all environmental surfaces as appropriate
- Remove bleach and all non approved chemicals from building
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate and repair cause of stained ceiling tile as appropriate
- Evaluate and repair HVAC to lower humidity level and raise temperature (South Area PPO notified on 7/22/05)
IAQ Assessment
July 21, 2005
Evaluation Requested
Silver Shores Elementary School
July 22, 2005
Evaluation Date
12:15 pm
Time of Day
Outdoor Conditions Temperature 91.1 53
Relative Humidity Ambient CO2 450
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
151 67.1 67.6 404 4
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In None
Ceiling Type No
No
Drywall
Wall Type None
No
No
12 x 12 Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling
Yes No No
Walls
Flooring Yes No No
HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant
HVAC Return Grills Yes No No
Ceiling at Supply No Yes Yes Clean with Wexcide disinfectant
Grills
Surfaces in Room Yes No No
Observations
Findings:
- Dust and debris on HVAC supply grills
- Dust and debris on ceiling at HVAC supply grills
- Elevated humidity level and low temperature
Recommendations:
Site Based Maintenance:
- Clean HVAC supply grills with Wexcide disinfectant solution
- Clean ceiling at HVAC supply grills as appropriate
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate and repair HVAC to lower humidity level and raise temperature (South Area PPO notified on 7/22/05)
IAQ Assessment
July 21, 2005
Evaluation Requested
Silver Shores Elementary School
July 22, 2005
Evaluation Date
12:15 pm
Time of Day
Outdoor Conditions Temperature 91.1 53
Relative Humidity Ambient CO2 450
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
152 66.4 69.3 408 4
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In None
Ceiling Type No
No
Drywall
Wall Type None
No
No
12 x 12 Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling
Yes No No
Walls
Flooring Yes No No
HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant
HVAC Return Grills Yes No No
Ceiling at Supply No Yes Yes Clean with Wexcide disinfectant
Grills
Surfaces in Room Yes No No
Observations
Findings:
- Dust and debris on HVAC supply grills
- Dust and debris on ceiling at HVAC supply grills
- Elevated humidity level and low temperature
Recommendations:
Site Based Maintenance:
- Clean HVAC supply grills with Wexcide disinfectant solution
- Clean ceiling at HVAC supply grills as appropriate
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate and repair HVAC to lower humidity level and raise temperature (South Area PPO notified on 7/22/05)
IAQ Assessment
July 21, 2005
Evaluation Requested
Silver Shores Elementary School
July 22, 2005
Evaluation Date
12:15 pm
Time of Day
Outdoor Conditions Temperature 91.1 53
Relative Humidity Ambient CO2 450
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
155 70.6 64.2 403 4
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In None
Ceiling Type No
No
Drywall
Wall Type None
No
No
12 x 12 Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling
Yes No No
Walls
Flooring Yes No No
HVAC Supply Grills Yes No No
HVAC Return Grills Yes No No
Ceiling at Supply No Yes Yes Clean with Wexcide disinfectant
Grills
Surfaces in Room No Yes Yes Clean as appropriate
Observations
Findings:
- Dust and debris on ceiling at HVAC supply grills
- Dust and debris on environmental surfaces
- Elevated humidity level and low temperature
Recommendations:
Site Based Maintenance:
- Clean ceiling at HVAC supply grills as appropriate
- Clean all environmental surfaces as appropriate
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate and repair HVAC to lower humidity level and raise temperature (South Area PPO notified on 7/22/05)
IAQ Assessment
July 21, 2005
Evaluation Requested
Silver Shores Elementary School
July 22, 2005
Evaluation Date
12:15 pm
Time of Day
Outdoor Conditions Temperature 91.1 53
Relative Humidity Ambient CO2 450
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
228 72.2 79 402 4
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In None
Ceiling Type No
No
Drywall
Wall Type None
No
No
12 x 12 Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling
Yes No No
Walls
Flooring Yes No No
HVAC Supply Grills Yes No No
HVAC Return Grills Yes No No
Ceiling at Supply No Yes Yes Clean with Wexcide disinfectant
Grills
Surfaces in Room No Yes Yes Clean as appropriate
Observations
Findings:
- Visible microbial growth on desks, doors and cabinets
- Dust and debris on ceiling at HVAC supply grills
- Dust and debris on environmental surfaces
- Elevated humidity level
Recommendations:
Site Based Maintenance:
- Wipe all desks, doors and cabinets with Wexcide disinfectant solution
- Clean ceiling at HVAC supply grills as appropriate
- Clean all environmental surfaces as appropriate
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate and repair HVAC to lower humidity level (South Area PPO notified on 7/22/05)
IAQ Assessment
July 21, 2005
Evaluation Requested
Silver Shores Elementary School
July 22, 2005
Evaluation Date
12:15 pm
Time of Day
Outdoor Conditions Temperature 91.1 53
Relative Humidity Ambient CO2 450
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
229 72.6 84 388 4
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In None
Ceiling Type No
No
Drywall
Wall Type Various
Yes
Yes
12 x 12 Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
No Yes Yes Clean as appropriate
Ceiling
No Yes Yes Clean as appropriate
Walls
Flooring Yes No No
HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant
HVAC Return Grills No Yes Yes Clean with Wexcide disinfectant
Ceiling at Supply No Yes Yes Clean with Wexcide disinfectant
Grills
Surfaces in Room No Yes Yes Clean as appropriate
Observations
Findings:
- Visible microbial growth on walls, desks, doors and cabinets
- Dust and debris on ceiling
- Dust and debris on HVAC supply and return grills
- Dust and debris on environmental surfaces
- Elevated humidity level
Recommendations:
Site Based Maintenance:
- Wipe all walls, desks, doors and cabinets with Wexcide disinfectant solution
- Clean ceiling as appropriate
- Clean HVAC supply and return grills with Wexcide disinfectant solution
- Clean all environmental surfaces as appropriate
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate and repair HVAC to lower humidity level (South Area PPO notified on 7/22/05)
IAQ Assessment
July 21, 2005
Evaluation Requested
Silver Shores Elementary School
July 22, 2005
Evaluation Date
12:15 pm
Time of Day
Outdoor Conditions Temperature 91.1 53
Relative Humidity Ambient CO2 450
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
231 72.1 80.4 406 4
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In None
Ceiling Type No
No
Drywall
Wall Type None
No
No
12 x 12 Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling
No Yes Yes Clean as appropriate
Walls
Flooring Yes No No
HVAC Supply Grills Yes No No
HVAC Return Grills Yes No No
Ceiling at Supply No Yes Yes Clean with Wexcide disinfectant
Grills
Surfaces in Room No Yes Yes Clean as appropriate
Observations
Findings:
- Visible microbial growth on walls, desks, doors and cabinets
- Dust and debris on ceiling at HVAC supply grills
- Dust and debris on environmental surfaces
- Elevated humidity level
- Glade plug in found in room
Recommendations:
Site Based Maintenance:
- Wipe all walls, desks, doors and cabinets with Wexcide disinfectant solution
- Clean ceiling at HVAC supply grills as appropriate
- Clean all environmental surfaces as appropriate
- Remove air freshener from room
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate and repair HVAC to lower humidity level (South Area PPO notified on 7/22/05)
|