SUBJECT: Indoor Air Quality (IAQ) Assessment
FISH 104
On September 6, 2007 I conducted an assessment FISH 104 at Indian Ridge Middle School. This evaluation
included observations of the flooring system, ceiling tiles, false ceiling plenum, environmental surfaces, interior
and exterior walls, and the accessible ventilation equipment. Additionally, environmental parameter
measurements were taken to include temperature, relative humidity, and carbon dioxide. The detailed
findings, along with the recommended corrective action can be found on the attached IAQ Assessment
Worksheets.
Generally, the IAQ Assessment did not identify any existing conditions significantly impacting IAQ and
thereby presenting immediate health and safety concerns to building occupants. However, due to individual
sensitivities and predisposing health factors, it is possible that some building occupants may elicit a health
response to agents and / or conditions identified during the evaluation. Therefore, to further improve IAQ,
prevent development of future IAQ-related problems, and to reduce the potential for IAQ-related complaints by
building occupants, the IAQ Assessment Team recommends appropriate follow up of each item identified and
listed in the attached evaluation.
Please ensure that your Head Facilities Serviceperson receives a copy of this correspondence so that the
recommendations requiring their attention can be addressed. Within two weeks a representative from the
Custodial/Grounds Department will conduct a follow-up visit to ensure that all issues have been appropriately
addressed.
Should any questions arise, or if the current concerns continue after the attached recommendations have been
addressed, please feel free to contact me at 754-321-3200.
cc: Dr. Verda Farrow, Area Superintendent
Margaret Underhill, Area Director
Jeffrey S. Moquin, Director, Risk Management
James Carballo, Project Manager, Facilities and Construction Management
Ralph Eckhardt, Broward Teachers Union
Roy Jarrett, Federation of Public Employees
Mark Dorsett, Manager 1, Physical Plant Operations Division, Zone 1
Roy Norton, Manager Custodial/Grounds, Physical Plant Operations Division
Robert Krickovich, Coordinator, LEA, Facilities and Construction Management
ES/tc
Enc.
The School Board of Broward County, Florida
3471
IAQ Assessment Location Number
September 4, 2007
Evaluation Requested
Indian Ridge Middle School
September 6, 2007
Evaluation Date
3:00 pm
Time of Day
Outdoor Conditions Temperature 89.1 56.7
Relative Humidity Ambient CO2 460
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
104 75.3 43 1184 3
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In None
Ceiling Type No
No
Drywall
Wall Type None
No
No
Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling
Yes No No
Walls
Flooring No Yes Yes Clean and sanitize
HVAC Supply Grills Yes No No
HVAC Return Grills Yes No No
Ceiling at Supply Yes No No
Grills
Surfaces in Room No Yes Yes Clean as appropriate
Observations
Findings:
- Environmental parameters were acceptable
- Dust and debris on floor between teachers' desk and window
- Dust build up on top shelf and counter
-Recommendations:
Site Based Maintenance:
- Clean and sanitize floor
- Clean top shelf and counter
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
|