TO: Mrs. Vered Roberts, Principal
Hollywood Hills Elementary School

FROM: Robert J. Krickovich, Coordinator, LEA
Facilities and Construction Management, Environmental Division

SUBJECT: Indoor Air Quality (IAQ) Assessment
Portable 701VE and 702VE

On September 15, 2006 I conducted an assessment of Portable 701VE and 702VE at Hollywood Hills
Elementary School. This evaluation included observations of the flooring system, ceiling tiles, false
ceiling plenum, environmental surfaces, interior and exterior walls, and the accessible ventilation
equipment. Additionally, environmental parameter measurements were taken to include
temperature, relative humidity, and carbon dioxide. The detailed findings, along with the
recommended corrective action can be found on the attached IAQ Assessment Worksheets.

The IAQ assessment did identify one or more existing conditions impacting IAQ and has generated
appropriate work orders to correct deficiencies in systems and maintenance that could contribute to
decreased indoor air quality. At the time of the assessment, these concerns were not an immediate
health or safety concern to building occupants. However, due to individual sensitivities and
predisposing health factors, it is possible that some building occupants may elicit a health response to
agents and / or conditions identified during the evaluation. Therefore, to further improve IAQ,
prevent development of future IAQ-related problems, and to reduce the potential for IAQ-related
complaints by building occupants, the IAQ Assessment Team recommends appropriate follow up of
each item identified and listed in the attached evaluation.

Should any questions arise, or if the current concerns continue after the attached recommendations
have been addressed, please feel free to contact me at 754-321-1638.

cc: Sam Gregg, Area Superintendent
Margaret Underhill, Area Director
Jeffrey S. Moquin, Director, Risk Management
Frank Girardi, Project Manager, Facilities and Construction Management
Diane Watts, Broward Teachers Union
Mark Dorsett, Manager 1, Physical Plant Operations Division, Zone 1
Roy Norton, Manager Custodial/Grounds, Physical Plant Operations Division

RK/tc
Enc.



The School Board of Broward County, Florida
0111
IAQ Assessment Location Number
September 15, 2006
Evaluation Requested
Hollywood Hills Elementary School

September 15, 2006
Evaluation Date
12:20 pm
Time of Day

Outdoor Conditions Temperature 89.8 56.9
Relative Humidity Ambient CO2 490

Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
P-701VE 81.8 48.9 2774 26
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In None
Ceiling Type No
No
Tackable
Wall Type None
No
No
Carpet
Flooring None
No No


Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling

Yes No No
Walls

Flooring Yes No No

HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant

HVAC Return Grills No Yes Yes Clean with Wexcide disinfectant

Ceiling at Supply Yes No No
Grills

Surfaces in Room No Yes Yes Clean as appropriate


Observations
Findings:
- Dust and debris on HVAC supply and return grills
- Temperature was elevated at the time of the assessment. Only East A/C unit was running. Fresh air vent was closed and was opened at the
time of the assessment.
- Dust build up on environmental surfaces
- Dust and debris on HVAC coils - East unit
- Elevated moisture content in walls under all windows and all of West wall
- Exterior - caulking missing around South door and around windows on North side
- Exterior - Fungus growing on West wall and T-1-11 is soft to the touch
- Exterior - Possible birds nesting above ceiling as evidenced by soffit screen in Norhwest corner of portable

Recommendations:
Site Based Maintenance:
- Clean HVAC supply and return grills with Wexcide disinfecrtant solution
- Ensure that both HVAC units are running and set to fresh air
- Thoroughly clean environmental surfaces
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as appropriate
Physical Plant Operations:
- Clean HVAC coils - East unit
- Evaluate cause of water intrusion and repair. Repair/replace wall material as appropriate (see above).
- Caulk around South door and around indows on North side
- Replace damaged T-1-11 on exterior of portable
- Seal birds out of the building - Northwest corner of portable
0111
IAQ Assessment Location Number
September 15, 2006
Evaluation Requested
Hollywood Hills Elementary School

September 15, 2006
Evaluation Date
12:20 pm
Time of Day

Outdoor Conditions Temperature 89.8 56.9
Relative Humidity Ambient CO2 490

Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
P-702VE 76.7 49.9 1811 22
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In 3 ceiling tiles
Ceiling Type No
Yes
Tackable
Wall Type None
No
No
Carpet
Flooring None
No No


Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
No Yes Yes Replace stained ceiling tiles
Ceiling

Yes No No
Walls

Flooring Yes No No

HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant

HVAC Return Grills No Yes Yes Clean with Wexcide disinfectant

Ceiling at Supply Yes No No
Grills

Surfaces in Room No Yes Yes Clean as appropriate


Observations
Findings:
- Dust and debris on HVAC supply and return grills
- Dust and debris on A/C filters
- Dust build up on environmental surfaces
- Dust and debris on HVAC coils - both units. Coils frozen on West unit.
- Elevated moisture content in East and West wall and South wall from restroom door to portable door
- Exterior - T-1-11 on West side is severely water damaged
- Exterior - T-1-11 patch on South side is allowing water into the building - entire length of the wall
- Exterior - caulking missing around windows and doors

Recommendations:

Site Based Maintenance:
- Clean HVAC supply and return grills with Wexcide disinfecrtant solution
- Remove and replace A/C filters
- Thoroughly clean environmental surfaces
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as appropriate

Physical Plant Operations:
- Clean HVAC coils - both units
- Evaluate cause of water intrusion and repair. Repair/replace wall material as appropriate (see above).
- Caulk around all doors and windows
- Replace damaged T-1-11 on exterior of portable as indicated above

Search    ENTER KEYWORD
ALL Chemical Property And Toxicity Analysis PAGES IN THIS GROUP
NAMECAS
broward_k12_fl_us---5-9-2005_survey_summary_report.asp N/A
broward_k12_fl_us---6-10-2005_fish_131.asp N/A
broward_k12_fl_us---6-8-2004_followup_physical_plant_operations_.asp N/A
broward_k12_fl_us---7-15-2005_portable_1277c.asp N/A
broward_k12_fl_us---7-21-2005_fish_801k_806_807_809_810_815.asp N/A
broward_k12_fl_us---7-22-2005_fish_150_151_152_155_228_229_231.asp N/A
broward_k12_fl_us---7-22-2005_portable_192.asp N/A
broward_k12_fl_us---7-28-2005_&_8-4-2005_fish_331_and_science_building.asp N/A
broward_k12_fl_us---8-15-2005_fish_704_705_706_707.asp N/A
broward_k12_fl_us---8-17-2007_fish_501_502_502a_502b_503.asp N/A
broward_k12_fl_us---8-17-2007_portable_164n_622p_873c_1105pk_1117pk.asp N/A
broward_k12_fl_us---8-21-2007_fish_320_and_320b.asp N/A
broward_k12_fl_us---8-22-2005_fish_508.asp N/A
broward_k12_fl_us---8-22-2007_fish_524.asp N/A
broward_k12_fl_us---8-31-2006_fish_401_401j_401k_401m_401p_401q_401r_central_textbook_warehouse.asp N/A
broward_k12_fl_us---8-4-2005_fish_806a.asp N/A
broward_k12_fl_us---8-4-2005_portable_43.asp N/A
broward_k12_fl_us---8-5-2005_fish_805_806_807_810.asp N/A
broward_k12_fl_us---8-8-2005_fish_117a_and_119a.asp N/A
broward_k12_fl_us---9-12-2006_fish_318_320b_portable_126.asp N/A
broward_k12_fl_us---9-14-2006_fish_119a_and_119b.asp N/A
broward_k12_fl_us---9-14-2007_fish_103a_104a_905_906.asp N/A
broward_k12_fl_us---9-15-2006_portable_701ve_and_702ve.asp N/A
broward_k12_fl_us---9-16-2005_fish_603_604b_803_810.asp N/A
broward_k12_fl_us---9-16-2007_fish_150c_152g_160_201.asp N/A
broward_k12_fl_us---9-18-2007_portable_302c_and_625c.asp N/A
broward_k12_fl_us---9-5-2007_fish_211_and_222_-_annex.asp N/A
broward_k12_fl_us---9-6-2007_fish_104.asp N/A
broward_k12_fl_us---apollomiddle.asp N/A
broward_k12_fl_us---arthurashemiddle.asp N/A
broward_k12_fl_us---art_-_calciun_sulfate_chalk.asp N/A
broward_k12_fl_us---art_-_chalk.asp N/A
broward_k12_fl_us---art_-_elmers_washable_school_glue.asp N/A
broward_k12_fl_us---art_-_prang_ready_to_use_paint.asp N/A
broward_k12_fl_us---art_-_school_smart_white_glue.asp N/A
broward_k12_fl_us---asthmacompanionpiece.asp N/A
broward_k12_fl_us---austin_a-1_bleach_regular_fresh_lemon_floral.asp 7681-52-9 1310-73-2
broward_k12_fl_us---banner_gl__fungicide.asp 60207-90-1
broward_k12_fl_us---barricade_65wg__herbicide.asp 29091-21-2
broward_k12_fl_us---barricade_65w_herbicide.asp 29091-21-2
broward_k12_fl_us---basagran_herbicide.asp 50723-80-3
broward_k12_fl_us---bennettelementary.asp N/A
broward_k12_fl_us---bethuneelementary.asp N/A
broward_k12_fl_us---bloodborne_pathogens_exposu.asp N/A
broward_k12_fl_us---boulevardheightselementary.asp N/A
broward_k12_fl_us---brighthorizon.asp N/A
broward_k12_fl_us---bug_bomb_claire_c-002.asp 64742-47-8 68476-86-8 74-98-6 106-97-8 75-28-5
broward_k12_fl_us---cafe_-_bio-12.asp N/A
broward_k12_fl_us---cafe_-_bio-swab.asp N/A
broward_k12_fl_us---cafe_-_fs_pot_and_pan_scrub.asp N/A

Free MSDS Search ( Providing 250,000+ Material Properties )
Chemcas.com | Ads link:HBCCHEM.INC