Jeffrey S. Moquin, Director Telephone: 754-321-3200
Risk Management Department Facsimile: 754-321-3290
August 10, 2005
TO: Mr. Edmond Wade, Principal
Blanche Ely High School
FROM: Robert J. Krickovich, Coordinator, LEA
Facilities and Construction Management, Environmental Division
SUBJECT: Indoor Air Quality (IAQ) Assessment
FISH 331 and Science Building
On July 28, 2005 and August 4, 2005 the IAQ Assessment Team conducted an assessment of FISH 331
and the Science Building at Blanche Ely High School. The evaluation consisted of a walkthrough of
the identified areas to assess the current condition of the location with regard to indoor air quality.
This assessment included observations of the carpet, floor tile, ceiling tile, interior walls, false ceiling
plenum, and accessible ventilation equipment.
Attached are the findings of this assessment along with recommendations for further assessment,
remediation, or corrective actions, if needed.
Generally, the IAQ Assessment did not identify any existing conditions significantly impacting IAQ
and thereby presenting immediate health and safety concerns to building occupants. However, due to
individual sensitivities and predisposing health factors, it is possible that some building occupants
may elicit a health response to agents and / or conditions identified during the evaluation. Therefore,
to further improve IAQ, prevent development of future IAQ-related problems, and to reduce the
potential for IAQ-related complaints by building occupants, the IAQ Assessment Team recommends
appropriate follow up of each item identified and listed in the attached evaluation.
Should any questions arise, or if the current concerns continue after the attached recommendations
have been addressed, please feel free to contact me at 754-321-1638.
cc: Dr. Joanne Harrison, Area Superintendent
Craig Anderson, Area Director
Jeffrey S. Moquin, Director, Risk Management
Rigo Zubizarreta, Project Manager II, Facilities and Construction Management
LaFrances Trotter, Broward Teachers Union
Mark Dorsett, Manager 1, Physical Plant Operations Division, Zone 1
Roy Norton, Manager Custodial/Grounds, Physical Plant Operations Division
RK/tc
Enc.
The School Board of Broward County, Florida
IAQ Assessment
July 28, 2005
Evaluation Requested
Blanche Ely High School
July 28, 2005
Evaluation Date
1:00 pm
Time of Day
Outdoor Conditions Temperature 92.1 66.5
Relative Humidity Ambient CO2 424
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
331 88.5 68.8 442 1
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In One stained tile in 330C
Ceiling Type No
Yes
Plaster
Wall Type None
No
No
12 x 12 Vinyl
Flooring None
No No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling
Yes No No
Walls
Flooring Yes No No
HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant
HVAC Return Grills N/A through door
Ceiling at Supply No Yes Yes Clean with Wexcide disinfectant
Grills
Surfaces in Room Yes No No
Observations
Findings:
- Visible microbial growth on wall in air handler room (330E)
- HVAC unit was turned off at time of assessment
- One stained ceiling tile in room 330C (outside of 330E)
- Dust and debris on HVAC supply grills
- Dust and debris on ceiling at HVAC supply grills
Recommendations:
Site Based Maintenance:
- Clean HVAC supply grills with Wexcide disinfectant solution
- Clean ceiling at HVAC supply grills
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate and repair cause of stained ceiling tile in room 330C and repair as appropriate and replace ceiling tile
- Evaluate and remove and replace damaged drywall in room 330E
- Evaluate HVAC unit for proper operation and instruct site based staff on proper operation of unit
IAQ Assessment
August 4, 2005
Evaluation Requested
Blanche Ely High School
August 4, 2005
Evaluation Date
12:00 pm
Time of Day
Outdoor Conditions Temperature 89.6 58.8
Relative Humidity Ambient CO2 423
Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
Science 72.1 56.3 441 2
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In Around exhaust fans
Ceiling Type Yes
Yes
Drywall
Wall Type None
No
No
12 x 12 Vinyl
Flooring Under exhaust fans
Yes No
Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
No Yes Yes Clean as appropriate
Ceiling
Yes No No
Walls
Flooring Yes No No
HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant
HVAC Return Grills No Yes Yes Clean with Wexcide disinfectant
Ceiling at Supply No Yes Yes Clean as appropriate
Grills
Surfaces in Room Yes No No
Observations
Findings: Entire Science Building
- Microbial growth on ceiling tiles around and under exhaust fan duct work
- Heavy dust and debris on ceiling and fire sprinklers
- Dust and debris on HVAC supply and return grills
- Heavy dust and debris on ceiling at HVAC supply grills
- One damper actuator not wired
- Building is in negative pressure
Recommendations:
Site Based Maintenance:
- Clean ceiling and fire sprinklers as appropriate
- Clean HVAC supply and return grills with Wexcide disinfectant solution
- Clean ceiling at HVAC supply grills as appropriate
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate
Physical Plant Operations Division:
- Evaluate HVAC for proper operation and check all controls and repair as appropriate
- Evaluate damper actuators for proper operation and repair as appropriate (one was not wired)
- Insulate duct as necessary and evaluate exhaust ducts for proper operation
- Replace all damaged ceiling tiles and check interlock of all exhaust fans
|