SUBJECT: Indoor Air Quality (IAQ) Assessment
Portable 164N, 622P, 873C, 1105PK, 1117PK

On August 17, 2007 I conducted a follow-up assessment of Portable 164N, 622P, 873C, 1105PK and 1117PK at
West Hollywood Elementary School. The assessment consisted of a reevaluation walkthrough of the
previously identified area to assess the current condition of the location with regard to indoor air quality. This
assessment included reviewing previously generated work orders as well as observation of the area of concern
as stated in the IAQ Assessments performed on April 27, 2007. Attached are the findings of this assessment
along with recommendations for further assessment, remediation, or corrective actions, if needed.

The IAQ assessment did identify one or more existing conditions impacting IAQ and has generated appropriate
work orders to correct deficiencies in systems and maintenance that could contribute to decreased indoor air
quality. At the time of the assessment, these concerns were not an immediate health or safety concern to
building occupants. However, due to individual sensitivities and predisposing health factors, it is possible that
some building occupants may elicit a health response to agents and / or conditions identified during the
evaluation. Therefore, to further improve IAQ, prevent development of future IAQ-related problems, and to
reduce the potential for IAQ-related complaints by building occupants, the IAQ Assessment Team recommends
appropriate follow up of each item identified and listed in the attached evaluation.

Please ensure that your Head Facilities Serviceperson receives a copy of this correspondence so that the
recommendations requiring their attention can be addressed. Within two weeks a representative from the
Custodial/Grounds Department will conduct a follow-up visit to ensure that all issues have been appropriately
addressed.

Should any questions arise, or if the current concerns continue after the attached recommendations have been
addressed, please feel free to contact me at 754-321-3200.

cc: Dr. Joel Herbst, Area Superintendent
Valerie Wanza, Area Director
Jeffrey S. Moquin, Director, Risk Management
Rodney Williams, Project Manager, Facilities and Construction Management
Diane Watts, Broward Teachers Union
Roy Jarrett, National Federation of Public and Private Employees
Mark Dorsett, Manager 1, Physical Plant Operations Division, Zone 1
Roy Norton, Manager Custodial/Grounds, Physical Plant Operations Division
Robert Krickovich, Coordinator, LEA, Facilities and Construction Management

ES/tc
Enc.



The School Board of Broward County, Florida
0161
IAQ Assessment Location Number
August 16, 2007
Evaluation Requested
West Hollywood Elementary School

August 17, 2007
Evaluation Date
Time of Day

Outdoor Conditions Temperature 86.5 87.2
Relative Humidity Ambient CO2 463

Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
P-164N 71.4 41.9 591 1
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
Yes
Noticeable Odor
damage / staining? growth? affected
Wood Paneling 1 Panel
Ceiling Type No
Yes
Tackable
Wall Type North Wall
No
Yes
Vinyl
Flooring None
No No


Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
No Yes Yes Repair/replace ceiling material
Ceiling

Yes No No
Walls

Flooring Yes No No

HVAC Supply Grills Yes No No

HVAC Return Grills Yes No No

Ceiling at Supply Yes No No
Grills

Surfaces in Room Yes No No


Observations
Findings:
- Visible staining on 1 ceiling panel
- Small gap at East door between door and frame
- One damaged floor tile at West door
- Visible staining on North wall under dry erase board and on board. Moisture content is not elevated.
- Elevated moisture content in South wall (18% WME) under A/C unit. Wall reveals signs of previous water damage. Possible
drain pan leak.

-Recommendations:

Site Based Maintenance:
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate

Physical Plant Operations:
- Evaluate cause of stained ceiling panel and repair as appropriate. Repair/replace ceiling material as appropriate.
- Evaluate gap at East door between door and frame and repair as appropriate to prevent water intrusion and introduction of
outside air
- Remove and replace damaged floor tile at West door
- Evaluate cause of elevated moisture content in South wall under A/C unit and staining on North wall under dry erase board and
repair as appropriate. Repair/replace wall material as appropriate.
0161
IAQ Assessment Location Number
August 16, 2007
Evaluation Requested
West Hollywood Elementary School

August 17, 2007
Evaluation Date
Time of Day

Outdoor Conditions Temperature 86.5 87.2
Relative Humidity Ambient CO2 463

Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
P-622P 73.2 51.6 524 4
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In 3 Ceiling Tiles
Ceiling Type No
Yes
Tackable
Wall Type 1 square foot
Yes
Yes
Vinyl
Flooring None
No No


Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
No Yes Yes Replace stained ceiling tiles
Ceiling

Yes No No
Walls

Flooring Yes No No

HVAC Supply Grills Yes No No

HVAC Return Grills Yes No No

Ceiling at Supply N/A
Grills

Surfaces in Room Yes No No


Observations
Findings:
- Elevated moisture and visible microbial on wall under A/C unit
- A/C unit leaking
- 3 stained ceiling tiles

-Recommendations:

Site Based Maintenance:
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate

Physical Plant Operations:
- Evaluate cause of elevated moisture content and microbial growth on wall under A/C unit and repair as appropriate (appears to
be leak from A/C unit). Repair/replace wall material as appropriate.
- Evaluate cause of stained ceiling tiles and repair as appropriate. Remove and replace ceiling tiles.
0161
IAQ Assessment Location Number
August 16, 2007
Evaluation Requested
West Hollywood Elementary School

August 17, 2007
Evaluation Date
Time of Day

Outdoor Conditions Temperature 86.5 87.2
Relative Humidity Ambient CO2 463

Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
P-873C 73.1 52.7 580 1
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
2 x 4 Lay In 2 Light Grids
Ceiling Type No
Yes
Tackable
Wall Type None
No
No
Vinyl
Flooring None
No No


Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling

Yes No No
Walls

Flooring Yes No No

HVAC Supply Grills Yes No No

HVAC Return Grills Yes No No

Ceiling at Supply Yes No No
Grills

Surfaces in Room Yes No No


Observations
Findings:
- 2 rusted light grids above South A/C wall unit
- Small gap at East door between door and frame
- Elevated moisture content in East wall (23% WME) under dry erase board. Wall reveals signs of previous repair.

-Recommendations:
Site Based Maintenance:
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate

Physical Plant Operations:
- Evaluate cause of rusted light grids above South A/C wall unit and repair as appropriate. Replace light grids.
- Evaluate gap at East door between door and frame and repair as appropriate to prevent water intrusion and introduction of
outside air
- Evaluate cause of elevated moisture content in East wall under dry erase board and repair as appropriate. Repair/replace wall
material as appropriate.
0161
IAQ Assessment Location Number
August 16, 2007
Evaluation Requested
West Hollywood Elementary School

August 17, 2007
Evaluation Date
8:45 am
Time of Day

Outdoor Conditions Temperature 86.5 87.2
Relative Humidity Ambient CO2 463

Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
P-1105PK 71 51.9 580
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
Yes
Noticeable Odor
damage / staining? growth? affected
4 x 10 Panels 6 A/C Supply Grills
Ceiling Type Yes
Yes
Wood
Wall Type None
No
No
Vinyl
Flooring None
No No


Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
Yes No No
Ceiling

Yes No No
Walls

Flooring Yes No No

HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant

HVAC Return Grills No Yes Yes Clean with Wexcide disinfectant

Ceiling at Supply Yes No No
Grills

Surfaces in Room Yes No No


Observations
Findings:
- Dust and debris, rust and microbial growth on all HVAC supply and return grills
- Bathroom has no exhaust fan
- Temperature was low at the time of the assessment

-Recommendations:
Site Based Maintenance:
- Clean HVAC supply and return grills with Wexcide disinfectant solution until PPO can facilitate replacement
- Adjust thermostat to increase temperature
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate

Physical Plant Operations:
- Evaluate cause of rust and microbial growth on A/C supply and return grills and repair as appropriate. Remove and replace all
supply and return grills.
- Evaluate need for exhaust fan in restroom
0161
IAQ Assessment Location Number
August 16, 2007
Evaluation Requested
West Hollywood Elementary School

August 17, 2007
Evaluation Date
Time of Day

Outdoor Conditions Temperature 86.5 87.2
Relative Humidity Ambient CO2 463

Temperature
Fish Relative Humidity CO2
Range # Occupants
Range
Range
P-1117PK 72.6 53 556 21
72 - 78 Max 700 > Ambient
30% - 60%
Visible water Visible microbial Amount of material
No
Noticeable Odor
damage / staining? growth? affected
3 x 10 Panels 4 Panels
Ceiling Type Yes
Yes
Wood
Wall Type None
No
No
Vinyl
Flooring None
No No


Needs
Clean Minor Dust
Corrective Action Required
Cleaning
/ Debris
No Yes Yes Repair/replace ceiling material
Ceiling

Yes No No
Walls

Flooring Yes No No

HVAC Supply Grills No Yes Yes Clean with Wexcide disinfectant

HVAC Return Grills No Yes Yes Clean with Wexcide disinfectant

Ceiling at Supply Yes No No
Grills

Surfaces in Room Yes No No


Observations
Findings:
- Visible staining on ceiling material in bathroom
- Visible staining and microbial growth on ceiling material on North side of room
- Dust and debris, rust and microbial growth on all HVAC supply and return grills

-Recommendations:
Site Based Maintenance:
- Clean HVAC supply and return grills with Wexcide disinfectant solution until PPO can facilitate replacement
- Continue to monitor this location for any signs of microbial growth as well as dust and debris accumulation and clean as
appropriate

Physical Plant Operations:
- Evaluate cause stained ceiling in bathroom and stained ceiling with visible microbial growth on North side of room and repair as
appropriate. Repair/replace ceiling material as appropriate.
- Evaluate cause of rust and microbial growth on A/C supply and return grills and repair as appropriate. Remove and replace all
supply and return grills.

Search    ENTER KEYWORD
ALL Chemical Property And Toxicity Analysis PAGES IN THIS GROUP
NAMECAS
broward_k12_fl_us---5-9-2005_survey_summary_report.asp N/A
broward_k12_fl_us---6-10-2005_fish_131.asp N/A
broward_k12_fl_us---6-8-2004_followup_physical_plant_operations_.asp N/A
broward_k12_fl_us---7-15-2005_portable_1277c.asp N/A
broward_k12_fl_us---7-21-2005_fish_801k_806_807_809_810_815.asp N/A
broward_k12_fl_us---7-22-2005_fish_150_151_152_155_228_229_231.asp N/A
broward_k12_fl_us---7-22-2005_portable_192.asp N/A
broward_k12_fl_us---7-28-2005_&_8-4-2005_fish_331_and_science_building.asp N/A
broward_k12_fl_us---8-15-2005_fish_704_705_706_707.asp N/A
broward_k12_fl_us---8-17-2007_fish_501_502_502a_502b_503.asp N/A
broward_k12_fl_us---8-17-2007_portable_164n_622p_873c_1105pk_1117pk.asp N/A
broward_k12_fl_us---8-21-2007_fish_320_and_320b.asp N/A
broward_k12_fl_us---8-22-2005_fish_508.asp N/A
broward_k12_fl_us---8-22-2007_fish_524.asp N/A
broward_k12_fl_us---8-31-2006_fish_401_401j_401k_401m_401p_401q_401r_central_textbook_warehouse.asp N/A
broward_k12_fl_us---8-4-2005_fish_806a.asp N/A
broward_k12_fl_us---8-4-2005_portable_43.asp N/A
broward_k12_fl_us---8-5-2005_fish_805_806_807_810.asp N/A
broward_k12_fl_us---8-8-2005_fish_117a_and_119a.asp N/A
broward_k12_fl_us---9-12-2006_fish_318_320b_portable_126.asp N/A
broward_k12_fl_us---9-14-2006_fish_119a_and_119b.asp N/A
broward_k12_fl_us---9-14-2007_fish_103a_104a_905_906.asp N/A
broward_k12_fl_us---9-15-2006_portable_701ve_and_702ve.asp N/A
broward_k12_fl_us---9-16-2005_fish_603_604b_803_810.asp N/A
broward_k12_fl_us---9-16-2007_fish_150c_152g_160_201.asp N/A
broward_k12_fl_us---9-18-2007_portable_302c_and_625c.asp N/A
broward_k12_fl_us---9-5-2007_fish_211_and_222_-_annex.asp N/A
broward_k12_fl_us---9-6-2007_fish_104.asp N/A
broward_k12_fl_us---apollomiddle.asp N/A
broward_k12_fl_us---arthurashemiddle.asp N/A
broward_k12_fl_us---art_-_calciun_sulfate_chalk.asp N/A
broward_k12_fl_us---art_-_chalk.asp N/A
broward_k12_fl_us---art_-_elmers_washable_school_glue.asp N/A
broward_k12_fl_us---art_-_prang_ready_to_use_paint.asp N/A
broward_k12_fl_us---art_-_school_smart_white_glue.asp N/A
broward_k12_fl_us---asthmacompanionpiece.asp N/A
broward_k12_fl_us---austin_a-1_bleach_regular_fresh_lemon_floral.asp 7681-52-9 1310-73-2
broward_k12_fl_us---banner_gl__fungicide.asp 60207-90-1
broward_k12_fl_us---barricade_65wg__herbicide.asp 29091-21-2
broward_k12_fl_us---barricade_65w_herbicide.asp 29091-21-2
broward_k12_fl_us---basagran_herbicide.asp 50723-80-3
broward_k12_fl_us---bennettelementary.asp N/A
broward_k12_fl_us---bethuneelementary.asp N/A
broward_k12_fl_us---bloodborne_pathogens_exposu.asp N/A
broward_k12_fl_us---boulevardheightselementary.asp N/A
broward_k12_fl_us---brighthorizon.asp N/A
broward_k12_fl_us---bug_bomb_claire_c-002.asp 64742-47-8 68476-86-8 74-98-6 106-97-8 75-28-5
broward_k12_fl_us---cafe_-_bio-12.asp N/A
broward_k12_fl_us---cafe_-_bio-swab.asp N/A
broward_k12_fl_us---cafe_-_fs_pot_and_pan_scrub.asp N/A

Free MSDS Search ( Providing 250,000+ Material Properties )
Chemcas.com | Ads link:HBCCHEM.INC